Gas Alarm Set GX-A1+CO Sensor

The professional CO detector with external sensor: Detect CO before entering the hazard area, display ppm accurately and shut off the hazard source

The Schabus CO detector GX-A1+CO is a professional CO warning system consisting of a control unit with plain-text display and an external, TÜV-tested CO sensor in accordance with DIN EN 50291 (CO in living spaces). The key advantage: the sensor is installed in the hazard area while the control unit is mounted outside. This allows the hazard situation to be assessed before entering the room. The name says it all: CO detected, danger averted.

The external sensor GX-5042 uses an electrochemical measuring cell and has its own alarm with LEDs, test button and buzzer. The control unit continuously displays the operating status and the CO concentration in ppm. In the event of an alarm, the system warns acoustically and optically both at the control unit and at the sensor itself, and simultaneously switches a potential-free 230 V changeover relay. This allows the hazard source to be shut off: the relay can start forced ventilation, close a solenoid shut-off valve or switch off the heating. A second potential-free changeover relay for faults up to 60 V DC reports technical faults to building management systems, home automation or monitoring systems.

The GX-A1+CO monitors carbon monoxide from incomplete combustion, for example from open fireplaces, Swedish stoves, gas boilers, barbecue systems and pellet bunkers. A cable break detection system immediately identifies damage to the sensor cable. The control unit and sensor are matched to each other and are supplied together.

⚠️

Important note: The GX-A1+CO and the sensor may only be installed in dry indoor rooms with residential-type use to ensure proper function. Installation must be carried out by a qualified specialist; please observe the five safety rules. The device must not be used in potentially explosive atmospheres and may only be used together with the supplied CO sensor. It is not approved for any use other than that described.

Safety at a distance

The GX-A1+CO combines a TÜV-tested external CO sensor with a control unit, two relay outputs and a plain-text display.

🫁

CO in precise ppm

The display continuously shows the operating status. The CO concentration is evaluated in precise ppm and continuously displayed on the control unit.

🧪

TÜV-tested to DIN EN 50291

The external CO sensor with electrochemical measuring cell is TÜV-tested to DIN EN 50291 and features high long-term stability.

📡

External sensor

The sensor is placed where CO is generated; the control unit remains outside the hazard area. This way you can see the reading before entering.

🚨

Dual alarming

Acoustic and optical warning at the control unit and additionally at the sensor itself with its own LEDs and buzzer.

🔁

Shutting off the hazard source

The 230 V alarm relay switches in the event of an alarm and controls forced ventilation, a solenoid shut-off valve or heating shut-off.

🏢

Fault relay for BMS

The second potential-free changeover relay (up to 60 V DC) reports faults to building management systems, home automation or monitoring systems.

🔌

Cable break detection

The device independently detects cable breaks, sensor failure and internal faults and reports them.

🖥️

Plain-text display

2-line plain-text display with operating status, CO value and further information that you can call up with the SERVICE button.

🔄

Self-test

A function check with sensor self-test runs when the device is switched on; it also restarts after a brief power failure.

🧪

Test button on the sensor

A short press checks the alarm sounder and LEDs; a long press causes the ppm display on the control unit to rise. Test gas is not required for regular testing.

🧰

Mounting material included

Screws, wall plugs and cable glands are included; nothing needs to be purchased separately.

🇩🇪

From the manufacturer

Made in Germany by Elektrotechnik Schabus, with 5-year warranty for registration and repair directly from the manufacturer.

What is included in the box

The set is ready for immediate use. Control unit and sensor are matched to each other.

  • GX-A1+CO warning device with external CO sensor GX-5042 and sensor cable
  • Mounting material: 4 large screws, 2 small screws and wall plugs
  • Cable glands: 2× M16 and 1× M12
  • Detailed operating instructions

The device has no options and no additional variants.

How the GX-A1+CO is constructed

The control unit with display, alarm sounder and relays is housed in a surface-mounted enclosure on the wall. The CO sensor is mounted separately at the desired location and connected via the sensor cable with RJ plug.

1

Housing with cover and base

The cover (front panel) is secured with four housing screws and is connected to the base via a ribbon cable with plug. The base is mounted on the wall. The piezo sounder is also located in the cover.

2

2-line plain-text display

The display continuously informs about the operating status. When a value exceeds 50 ppm, the exact ppm value also appears on the main screen. Use the SERVICE button to scroll to further information that is permanently stored and cannot be reset.

3

Status indicators (LEDs)

Three LEDs indicate the status: OPERATE for operation, ERROR for a technical fault (yellow) and ALARM for the alarm.

4

SERVICE and RESET | TEST buttons

Use SERVICE to call up the display information and, in the event of a fault, the error code. Use RESET | TEST to mute the alarm tone on the control unit in the event of an alarm.

5

Piezo sounder

The alarm sounder in the control unit warns loudly and piercingly, in addition to the optical indication in the event of an alarm.

6

External CO sensor GX-5042

The sensor with electrochemical measuring cell has its own LEDs, a test button and a buzzer and alarms independently of the control unit. The sensor cable (white, 3-core) ends in an RJ plug that is plugged into the sensor. The other end is routed into the control unit via a cable gland.

7

Mains connection terminals

The screw terminals for L, N and PE are each duplicated and interconnected. This makes it easier to bridge to the relay, for example for a solenoid shut-off valve.

8

Relays Re1 and Re2

The alarm relay Re1 is on the left, the fault relay Re2 on the right. Both are potential-free changeover contacts with terminals G (common), Ö (normally closed) and S (normally open). Two fuses for the relays are located on the circuit board.

9

Sensor connection

The sensor connection has the terminals +5, S, M and +24. Note the colour coding of the sensor cable: S = white, M = brown, +24 = green. Terminal +5 is not used.

Alarm according to DIN EN 50291 and shut-off

The monitoring system is set very sensitively for its purpose and warns at the CO concentrations specified in DIN EN 50291 (CO in living spaces).

🚨

Alarm

As soon as an alarm threshold is reached and the associated delay time has elapsed, the control unit and sensor alarm acoustically and optically.

🔁

Shut-off

In the event of an alarm, the control unit additionally switches relay Re1. This allows gas supply, heating or ventilation to be controlled in a targeted manner.

🔇

Muting

The acoustic alarm can be muted using the TEST button on the sensor or the RESET | TEST button on the control unit.

When the CO level falls below 50 ppm, the detector resets itself.

Alarm delay times according to DIN EN 50291

DIN EN 50291 specifies alarm delay times depending on the gas concentration. During development of the sensor, the shorter times were given preference.

  • From 30 ppm, no alarm may occur within 120 minutes
  • From 50 ppm, no alarm may occur within 60 minutes; the device alarms after 90 minutes at the latest
  • From 100 ppm, no alarm may occur within 10 minutes; the device alarms after 40 minutes at the latest
  • From 300 ppm, the device alarms after 3 minutes at the latest

Relay states

  • In monitoring mode the relay is energised (normally open contact closed, normally closed contact open)
  • In alarm mode the relay de-energises (normally open contact open, normally closed contact closed)

Correct installation and commissioning

Control unit and sensor are mounted at different locations: the sensor in the hazard area, the control unit outside.

⚠️

Installation must be carried out by a qualified specialist. Please observe the five safety rules. The connection cables leading to the gas detector must be permanently installed as surface-mounted wiring.

Wall mounting of the control unit

  1. Loosen the four housing screws and remove the front panel.
  2. If necessary, unplug the ribbon cable at the connector.
  3. Mount the base of the housing on the wall using the supplied mounting material.

Position of the external sensor

⚠️

Pay particular attention to the mounting height! Involve your chimney sweep in your planning and seek advice on the optimum mounting height.

  • The sensor detects only carbon monoxide CO
  • CO escaping from gas boilers or similar sources is initially warm and rises
  • CO that has equalised to room temperature is slightly heavier than air and sinks towards the floor
  • The DIN standard refers to the average nose height of people who regularly occupy the room
  • Depending on the source, mounting at breathing height or near the floor is appropriate; if in doubt, ask your chimney sweep

Mains connection and sensor cable

  • The cable from the house supply is connected to terminals L, N and PE, which are each duplicated and interconnected
  • The sensor cable is 2.5 m long, 3-core and ends in an RJ plug
  • The sensor cable can be extended up to 20 metres with 3 × 1.5 mm²
  • When connecting at the sensor connection: S = white, M = brown, +24 = green, +5 remains unused

Connecting the potential-free relays

  • Re1 (left, “Alarm”) switches up to 230 V, Re2 (right, “Fault”) up to 60 V DC
  • Both are potential-free changeover contacts with terminals G (common), Ö (normally closed) and S (normally open)
  • The switching current of 5 amperes must never be exceeded
  • In the connection example in the operating instructions, Re1 controls a solenoid shut-off valve that is closed in the idle state
  • For connection details, refer to the installation instructions of the connected device

Commissioning and function test

  1. Apply mains voltage. An electrical function check and a short initialisation phase take place until the sensor has been checked and the sensor self-test has been successfully completed.
  2. The display message “CO : Ready” confirms the successful test.
  3. The system then monitors the room.

Even after a brief power failure, the function check is restarted. For your safety, the manufacturer recommends regularly checking the system for correct function.

Test the system regularly

The test is carried out using the test button on the sensor. Further tests, for example with test gas, are not required for regular testing.

How to test the GX-A1+CO

  1. Briefly press the test button on the sensor: the sensor’s alarm sounder sounds and all LEDs function.
  2. Press the test button longer: the ppm display on the GX-A1+CO rises and the control unit also alarms.
  3. Check whether connected devices such as solenoid shut-off valve, ventilation or building management system respond as intended.

Behaviour in the event of an alarm

  1. Ventilate the room and switch off the CO source to ensure that no further gas can escape.
  2. Inform other people to leave the room.

Faults, error codes and care

Detecting and rectifying faults

  • The control unit detects its own technical faults and indicates them with an error code or a yellow flashing LED
  • Relay Re2 switches and informs, for example, the building management system
  • It can take up to one minute for the relay to switch because the device first attempts to rectify the fault by internal restarting
  • Disconnect the device from the mains for at least 1 minute and then restart it
  • If the fault cannot be rectified, use the SERVICE button to call up the page with the error code and contact support

Error codes

  • 1: internal supply voltage too low
  • 2: mains supply too low
  • 3: sensor or sensor cable defective
  • 4 to 9: the yellow, red or green LED cannot be switched on or off
  • 10 and 11: internal output fault
  • 12: sensor test failed
  • 21: memory initialisation failed, yellow LED flashes slowly
  • 22: internal software fault, yellow LED flashes slowly
  • 23: ambient temperature too low, yellow LED lights continuously
  • 24: ambient temperature too high, yellow LED lights continuously
  • 25: sensor test failed, yellow LED flashes rapidly
  • 26: temperature sensor fault, yellow LED flashes slowly
  • 27: memory fault detected, yellow LED flashes slowly

For codes 1 to 12 there is no special LED indication.

Maintenance

The sensor is generally maintenance-free. Only occasionally remove coarse dirt or dust from the device and keep the device and sensor free from moisture. The sensor’s service life depends on temperature and humidity: up to 10 years at a maximum of 28 °C and at least 30 % rH, up to 6 years at a maximum of 40 °C and at least 40 % rH.

Cleaning and care

  • Avoid the influence of moisture (splash or rain water), dust and direct sunlight on the device
  • Clean only with a dry linen cloth; if heavily soiled it may be slightly dampened
  • Do not use solvent-based cleaning agents

Manufacturer’s notes

  • Read the operating instructions carefully before installation and commissioning and keep them; they form part of the product
  • Installation must be carried out by a qualified specialist; please observe the five safety rules
  • Operate the control unit and sensor only together and exclusively in dry indoor rooms with residential-type use, for example living rooms, shops, stores, offices, low-dust workshops and seminar rooms
  • The CO gas warning device may only be used together with the supplied CO sensor
  • Do not use in potentially explosive atmospheres
  • The device is not approved for any use other than that described
  • Intended for residential buildings and living areas, sales areas such as shops and hypermarkets, and rooms of small businesses such as workshops and service centres; all installation locations are connected to the public low-voltage network
  • The connection cables to the gas detector must be permanently installed as surface-mounted wiring
  • The device contains no parts that you need to maintain
  • Packaging material is not a toy and does not belong in children’s hands
  • The manufacturer accepts no liability for damage or losses of any kind resulting from the failure to give an alarm signal despite elevated gas concentration
  • The declaration of conformity is available for download on the manufacturer’s website

Warranty, guarantee and disposal

The GX-A1+CO is covered by the statutory warranty of at least 2 years in the EU. Manufacturer Elektrotechnik Schabus additionally offers a 5-year guarantee that can be registered online. Repair and spare parts are available directly from the manufacturer, even beyond the statutory warranty. The prerequisite is that the device has been used in accordance with the operating instructions. The manufacturer accepts no liability for damage caused by accident, misuse, modification or negligence. If your device is defective, please contact the manufacturer and provide your full address and the reason for return.

The GX-A1+CO does not belong in household waste. The crossed-out wheeled bin symbol on the product reminds you to use the take-back systems for waste electrical and electronic equipment (WEEE Reg. No. DE91394868). This allows the materials to be reused in an environmentally friendly manner at the end of their service life. Information on collection, reuse and recycling systems is available from your local waste advisory service or from the manufacturer.

Why the GX-A1+CO is suitable

Safety at a distance

Sensor in the hazard area, control unit outside: status monitoring and early warning before entering.

Standards-tested

External CO sensor TÜV-tested to DIN EN 50291.

Shuts off the hazard

230 V relay for forced ventilation, solenoid shut-off valve or heating shut-off, second relay for faults.

Optimally positionable

The sensor is mounted where CO is generated, independently of the control unit.

Precise ppm

CO concentration on the plain-text display, continuously shown on the control unit.

Dual alarm

Acoustically and optically at the control unit and additionally at the sensor.

Cable-break protected

Independently detects cable damage, sensor failure and internal faults.

From the manufacturer

Made in Germany, 5-year guarantee registrable, repair and spare parts directly from the manufacturer.

Application areas

  • Open fireplaces and Swedish stoves: sensor next to the fire, control unit outside
  • Pellet bunkers: relay starts forced ventilation in the event of CO
  • Boiler rooms
  • Gas boiler rooms and gas cookers
  • Barbecue systems and open fires, for example in the catering trade
  • Technical rooms
  • Storage rooms with combustion sources
  • Rooms with CO risk that should not be entered
  • Shutting off the gas supply or heating in the event of CO
  • Connection to building management systems, home automation and monitoring systems

The Schabus CO detector GX-A1+CO: CO detected, danger averted.

Frequently asked questions

Which gas does the GX-A1+CO detect?

The external sensor detects only carbon monoxide (CO) from incomplete combustion. It does not react to other gases.

What is the advantage of the external sensor?

The sensor is installed in the hazard area, the control unit outside. This way you can see the CO concentration before entering the room. In addition, the sensor can be optimally positioned independently of the control unit.

For which rooms is the GX-A1+CO intended?

For dry indoor rooms with residential-type use, for example living rooms, shops, stores, offices, low-dust workshops and seminar rooms. Typical application areas are rooms with a fireplace, Swedish stove, gas boiler or pellet bunker, boiler rooms and technical rooms. It must not be used in potentially explosive atmospheres.

What happens in the event of an alarm?

Control unit and sensor alarm acoustically and optically, and alarm relay Re1 switches. This can, for example, close a solenoid shut-off valve, start forced ventilation or switch off the heating.

Can the alarm tone be muted?

Yes. The acoustic alarm can be muted using the TEST button on the sensor or the RESET | TEST button on the control unit. When the CO level falls below 50 ppm, the detector resets itself.

How quickly does the GX-A1+CO alarm?

The alarm delay follows DIN EN 50291 and depends on the concentration. From 300 ppm the device alarms after 3 minutes at the latest. During development of the sensor, the shorter times were given preference.

Where do I mount the sensor?

Pay attention to the mounting height. Warm CO from gas boilers rises, CO at room temperature sinks towards the floor. The DIN standard refers to average nose height. Involve your chimney sweep in the planning and seek advice on the optimum mounting height.

How long is the sensor cable and can I extend it?

The sensor cable is 2.5 m long, 3-core and has an RJ plug. It can be extended up to 20 metres with 3 × 1.5 mm². Note the colour coding: S = white, M = brown, +24 = green.

How do I test the GX-A1+CO?

Briefly press the test button on the sensor to check the alarm sounder and LEDs. With a longer press the ppm display on the GX-A1+CO rises and the device also alarms. Test gas is not required for regular testing.

What does “CO : Ready” mean?

The display message confirms that the function check on application of mains voltage and the sensor self-test have been successfully completed.

From when does the display show the exact ppm value?

From 50 ppm CO the exact ppm value is also shown on the main screen. Further information is available by scrolling through the displays with the SERVICE button.

What to do in the event of a fault?

The yellow LED flashes or an error code appears, and relay Re2 also switches. Disconnect the device from the mains for at least 1 minute and restart it. If the fault cannot be rectified, use the SERVICE button to call up the error code and contact support.

Does the device detect a cable break?

Yes. The cable break detection system immediately identifies damage to the sensor cable. The device also independently detects sensor failure and internal faults and reports them via the fault relay.

How long does the sensor last?

Up to 10 years at a maximum of 28 °C and at least 30 % rH, up to 6 years at a maximum of 40 °C and at least 40 % rH. The sensor is generally maintenance-free.

Is self-installation possible?

Installation must be carried out by a qualified specialist who observes the five safety rules. The mains connection and relay connections are electrical work.

How long is the warranty valid?

The statutory warranty of at least 2 years applies in the EU. In addition, manufacturer Schabus offers a 5-year guarantee that can be registered online.

Questions about the Schabus CO detector GX-A1+CO?

Our support team in Germany advises you free of charge on selection, installation and configuration.

Datasheets
Datasheet 1

Oops! Your browser doesn't support PDFs!

Datasheet 1 (2.19 MB)

Gas Alarm Set GX-A1 + CO Sensor

The GX-A1 Gas Alarm Set with external CO sensor provides precise and reliable monitoring of carbon monoxide in indoor environments. Thanks to its electrochemical sensor technology, robust control unit, and flexible connection options, it is suitable for residential, commercial, and technical applications.

Technical Data

  • Operating voltage: 100–240 V AC, 50–60 Hz
  • Power consumption: max. 10 VA (depending on operating mode)
  • Sensor operating voltage: 24 V, max. 50 mA (green + / brown -)
  • Protection class: IP20 (optional: IP65 device, IP54 sensor)
  • Sensor technology: electrochemical
  • Evaluation: PWM, microcontroller-based, ppm-accurate
  • Sound pressure: 85 dB(A) @ 1 m
  • Operating range (device): -15 °C to +40 °C, 10–90 % rH (non-condensing)
  • Operating range (sensor): 0 °C to +60 °C, 10–90 % rH (non-condensing)
  • Sensor lifetime: up to 6 years at max. 40 °C / min. 40 % rH; up to 10 years at max. 28 °C / min. 30 % rH
  • Dimensions control unit (H×W×D): 80 × 160 × 55 mm
  • Dimensions sensor (H×W×D): 88 × 58.5 × 39 mm
  • Cable: 2.5 m, Ø 3.5 mm, 3-core, RJ connector; extendable up to 20 m with 3 × 1.5 mm² wiring

Relays

  • Alarm relay (Re1): 250 V AC / 5 A (potential-free changeover)
  • Fault relay (Re2): 60 V DC / 5 A (potential-free changeover)
  • Switching capacity: Re1 "Alarm" 250 V AC / 5 A, Re2 "Error" 60 V DC / 5 A

Sensor

  • Sensor type: electrochemical, external sensor
  • No sensitivity to: other gases (CO-specific)

Manufacturer information:

Electrical engineering Schabus GmbH & Co. KG

Baierbacher Straße 150

83071 Stephanskirchen
Germany

Telephone: +49 80 36 / 674 979 – 0

Email: info@elektrotechnik-schabus.de

Responsible person:

Didactum® Security GmbH

Im Mühlenfeld 4

48163 Münster
Deutschland

Fon: (+49) 250 19 71 63 54 / (+49) 171 33 11 577

Email: info@didactum-security.de

Questions?

You have questions about Schabus products?

You would like a quote?

Contact us