The proven fork sensor with two nickel-plated brass contacts and 6 metres of cable, extendable up to 50 metres, for regularly dry environments: the Schabus water sensor SHT 5006 for Schabus water detectors
The Schabus water sensor SHT 5006 reports water as soon as conductive water connects both contacts at the same time. The two nickel-plated brass contacts are firmly cast in white plastic. The connected Schabus water detector evaluates the connection and immediately triggers the configured response.
Thanks to the wide notch (fork design), the sensor reliably detects genuine leaks, even in environments where biofilms, thin water films or condensation can form. False alarms caused by slight moisture are thus prevented. The compact design is suitable for point monitoring, hard-to-reach places and confined spaces.
The SHT 5006 is an accessory for the Schabus water detectors SHT 5000, SHT 5001 and SHT 5002. The sensor works passively and does not emit its own alarm.
Important note: The SHT 5006 is intended for regularly dry installation locations. It is not suitable for permanently damp or flooded areas such as shafts, tanks or cisterns. For these applications the manufacturer recommends mini float switches in plastic, V2A or V4A. The sensor must not be connected directly to a supply voltage or an electrical load, but only to a suitable sensor input of a water detector.
Good to know: Evaluation and subsequent function are handled by the connected water detector. Check the water detection after installation at the actual place of use.
Small, reliable, extendable
The SHT 5006 combines two measuring contacts with a long cable that fits directly onto Schabus water detectors.
Two nickel-plated brass contacts
The contacts are injection-moulded into white plastic. The alarm is triggered as soon as water connects both contacts.
Fork design
The wide notch distinguishes genuine leaks from slight moisture and prevents false alarms.
6 metres, extendable up to 50 metres
The 2 × 0.14 mm² LIYY cable is permanently cast. Special lengths are available on request.
For confined spaces
The compact sensor also fits in hard-to-reach places and confined spaces.
Passive design
The sensor requires no separate power supply. The water detector measures the connection between the contacts.
Robust LIYY cable
Flame-retardant, self-extinguishing, low-adhesion and largely resistant to oils, greases, coolants and lubricants.
Compatible with Schabus water detectors
Accessory for SHT 5000, SHT 5001 and SHT 5002.
Mounting material included
One screw and one wall plug are included.
What’s in the box
The SHT 5006 is ready for immediate use. The device has no options and no additional variants.
- Fork sensor SHT 5006
- 6 m LIYY control cable, 2 × 0.14 mm², permanently cast
- Mounting material (1 screw, 1 wall plug)
- Operating instructions
How the SHT 5006 is constructed
Contacts, housing and cable form one cast unit. Cast components must not be opened.
Fork-shaped sensor body
The body is made of white plastic. Its wide notch separates the two contacts and gives the fork sensor its name.
Two nickel-plated brass contacts
The two contacts are located at the fork ends and are firmly cast into the plastic. Both must be reached by water for the water detector to detect water.
Permanently connected two-core cable
The white LIYY cable is 6 m long, permanently cast and has two cores (brown and white) of 0.14 mm² each. It is connected to the two-pole sensor input of the water detector.
How the SHT 5006 detects water
Schabus water detectors work as impedance or resistance measuring devices: if a resistance below 80 kΩ is detected at a sensor input, the device evaluates this as water.
Contacts dry
There is no conductive connection. The water detector evaluates “no water”.
Contacts wetted
Conductive water connects both contacts. The water detector evaluates “water detected” and triggers the configured response.
No own alarm
The sensor does not generate a warning signal. Alarm and display come from the water detector.
Why thin cables?
The measurement is performed with a 120 Hz square-wave alternating voltage. Therefore the sensor cables must be very thin.
Place, connect, test
Both contacts must be able to be reached by escaping water.
Placement
- Determine the leak location. Position the sensor where escaping water is expected first, for example under washing machines or dishwashers, at pipelines or on floor surfaces.
- Align the contacts so that both can be reached by water.
- Secure the position and cable against unintentional movement.
- Protect the cable against crushing, tension and sharp edges.
Connection
- Identify the water detector (SHT 5000, SHT 5001 or SHT 5002). The connection terminals are described in its operating instructions.
- Connect the two-core cable to the designated sensor input.
- Carry out extensions and connections suitable for the respective environment and protect them against moisture.
- Check the entire detection chain: water detection, display, acoustic alarm and intended subsequent function.
Notes on the cable
- Use thin, unshielded LIYY cable, max. 2 × 0.14 mm²
- Total lengths of up to 50 m are possible; the existing 6 m are included
- When connected in parallel, the individual cable lengths are added together
- The maximum permissible cable capacitance is 10 nF
- Never run parallel to 230 V mains cables
- The cable is only briefly water-resistant
Commissioning
- Visually check fastening, cable and contacts.
- Deliberately wet both contacts with water. The test must show that water actually reaches the contacts at the installation site.
- Observe the indication on the water detector and the intended subsequent function.
- Dry the contacts and mounting surface. Check the return to normal status and, if applicable, the acknowledgement on the water detector.
Manufacturer’s notes
- Read the instructions for the sensor and those of the connected water detector and keep both
- Work on mains voltage may only be carried out by qualified electricians; isolate and verify absence of voltage beforehand
- Never connect low-voltage models to mains voltage
- Do not connect passive water sensors directly to a supply voltage or an electrical load
- Do not continue to use damaged cables or housings; do not open cast components
- Keep packaging material away from children
- The sensor only detects conductive water at its two contacts; for larger areas the sensor cable SHT 5020 is recommended
- It is not a level sensor; for fill levels use mini float switches
- Very pure water and condensate may not be detected reliably
- Specifications for float switches do not automatically apply to electrode sensors
Clean, check, find faults
Cleaning and re-checking
- Clean with a soft, damp cloth
- Do not use solvent-based agents
- Remove deposits from the contacts and dry the sensor
- Repeat the function test after cleaning, changes to the mounting or connection work
Troubleshooting
No reaction?
Check the model, connection and sensor input and whether both contacts are being wetted.
Indication remains?
Check for residual water, deposits and acknowledgement on the water detector.
Unexpected indication?
Check connections for moisture and the cable routing.
If the fault persists, put the system into a safe state and contact Schabus Support.
In the event of a service case
- Describe the fault as precisely as possible: What happened, when does it occur and what does the device display?
- The manufacturer will examine your enquiry and advise the next steps. Many questions can be clarified by telephone or e-mail.
- After consultation, pack securely against breakage and enclose a description of the fault, contact details and a copy of the proof of purchase.
The manufacturer cannot accept unpaid shipments. Repairs and maintenance may only be carried out by the manufacturer or authorised specialist personnel.
The SHT 5006 is covered by the statutory warranty of at least 2 years in the EU. The manufacturer Elektrotechnik Schabus additionally offers a 5-year guarantee that can be registered online. Repair and spare parts are available directly from the manufacturer, even beyond the statutory warranty. The device bears the CE mark; the EU declaration of conformity is available for download from the manufacturer.
The SHT 5006 does not belong in household waste. In accordance with Directive 2012/19/EU (WEEE) the device must be collected separately at the end of its service life and recycled in an environmentally sound manner, for example via a municipal collection point for electrical equipment (WEEE Reg. No. DE91394868).
Areas of application
- Laundry rooms and basements
- Under washing machines and dishwashers
- At pipelines
- Technical rooms and server rooms
- Floor surfaces
- Hard-to-reach places and confined spaces
The Schabus water sensor SHT 5006: the proven fork sensor for dry environments.
Frequently asked questions
How does the SHT 5006 detect water?
Conductive water connects the two nickel-plated brass contacts. The connected water detector detects this connection and triggers the configured response. The SHT 5006 itself has no acoustic alarm.
Which water detectors can I use the sensor with?
The SHT 5006 is intended as an accessory for the Schabus water detectors SHT 5000, SHT 5001 and SHT 5002. It is connected to the designated sensor input. Please observe the operating instructions of the respective device variant.
For which locations is the sensor suitable?
For regularly dry areas where escaping water should be detected early, for example under washing machines and dishwashers, at pipelines or in technical rooms. For permanently wet or flooded areas and for level monitoring, use a suitable float switch.
How should I place the fork sensor?
Mount it where escaping water is expected first. Both contacts must be able to be reached by water. Secure the sensor and cable against unintentional movement and check water detection at the actual installation site.
How long is the cable and can I extend it?
The permanently connected cable is 6 m long and has 2 × 0.14 mm². Taking into account the specifications of the connected water detector, a total cable length of up to 50 m is possible; the existing 6 m are included. Use a thin, unshielded LIYY cable with a maximum of 2 × 0.14 mm². When connected in parallel, the individual cable lengths are added together. Do not run sensor cables parallel to 230 V mains cables. Special lengths are available on request.
Does the sensor also detect thin water films or condensation?
What matters is the conductivity of the water and the connection between both contacts. Even a thin water film can trigger an indication if it connects both contacts sufficiently conductively. Very pure water or condensate may not be detected reliably. Therefore install the sensor in a location that is dry under normal operating conditions.
Is the cable water-resistant?
The LIYY connection cable is only briefly water-resistant and is not intended for permanent underwater use.
Can the SHT 5006 switch a pump or valve directly?
No. The passive water sensor is connected exclusively to a suitable sensor input. It must not be connected directly to a supply voltage or an electrical load. Any desired subsequent function is handled by the connected water detector or the downstream control system.
How do I check and clean the sensor?
Wet both contacts with water and check the reaction of the water detector as well as the intended subsequent function. Then dry the contacts and mounting surface and check the return to normal status. For cleaning, use a soft, damp cloth without solvent-based cleaning agents. Remove deposits and repeat the function test after cleaning, changes to the mounting or connection work.
Are there options or additional variants?
No. The SHT 5006 has no options. With the permanently connected cable it is complete.
How long is the warranty?
The statutory warranty of at least 2 years applies in the EU. In addition the manufacturer Schabus offers a 5-year guarantee that can be registered online.
Questions about the water sensor SHT 5006?
Our support team in Germany will be happy to advise you free of charge on selection, installation and configuration.
Water Sensor SHT 5006 Fork Sensor
Technical Data
- Operating range: −5 to +55 °C
- Dimensions (WxHxD): 50 × 28 × 7 mm
- Operating principle: Impedance measurement, passive
- Application area: Bathrooms, boiler rooms, kitchens, tea kitchens, washrooms
- Environmental conditions: Regularly dry environment
- Mounting: Wall mounting
Sensor & Contacts
- Sensor: 2 nickel-plated brass contacts
- Switching voltage: 25 V AC / 60 V DC, max 500 mA
- Cable: 6 m, 2 × 0.14 mm², white, Ø 3.2 mm, special lengths on request
- Material: Robust plastic compound
Manufacturer information:
Electrical engineering Schabus GmbH & Co. KG
Baierbacher Straße 150
83071 Stephanskirchen
Germany
Telephone: +49 80 36 / 674 979 – 0
Email: info@elektrotechnik-schabus.de
Responsible person:
Didactum® Security GmbH
Im Mühlenfeld 4
48163 Münster
Deutschland
Fon:
(+49) 250 19 71 63 54 / (+49) 171 33 11 577
Email: info@didactum-security.de