The Universal Gas Alarm Control Unit for Surface Mounting: Evaluation Unit for External Gas Sensors with Plain-Text Display, Two Relay Outputs and 48-Hour Relay Release
The Schabus GAS ALARM GX-A1+ is the control unit for a wide range of gas sensors and is used for professional gas monitoring indoors. It is the evaluation unit for an external gas sensor and already warns at a gas concentration that is far below life-threatening values. Depending on the connected sensor type, it monitors natural, town and liquid gases such as methane, propane, butane and ethanol, carbon dioxide (CO₂) as well as refrigerants such as R32, R404a or R410a.
The GX-A1+ supplies the sensor with operating voltage, controls the heating current if required and continuously evaluates the sensor voltage. In the event of an alarm it warns acoustically with a loud piezo signal generator and optically with flashing display illumination. At the same time a potential-free change-over relay switches, with which you can control for example a magnetic shut-off valve, a gas boiler or a ventilation system. A second relay reports technical faults that the device itself detects.
The sensor can be optimally positioned independently of the mounting height of the control unit. The GX-A1+ is the 100 % compatible successor to the GX-A1 with identical connection positions and replaces it in existing installations without rewiring.
Important note: The GX-A1+ is supplied without a sensor. For each gas type a suitable sensor must be selected and ordered separately. Installation must be carried out by a qualified specialist, and the connection cables to the gas detector must be installed firmly as surface wiring. The device must not be used in potentially explosive atmospheres.
Good to know: In the event of a sensor failure, heating systems or connected systems do not have to be switched off immediately. The integrated 48-hour relay release keeps the alarm relay energised for 48 hours; the remaining time is shown on the display. This leaves enough time to obtain the replacement sensor.
Detect, Warn, Shut Off
The GX-A1+ combines flexible sensor selection with clear alarming, an informative display and potential-free relay outputs.
For a Wide Range of Gases
Depending on the sensor, suitable for natural and town gas, liquid gas, carbon dioxide, hydrogen and refrigerants.
Sensor Freely Placeable
The external sensor can be optimally positioned independently of the mounting height of the control unit.
Acoustic and Optical Alarm
Loud piezo signal generator and flashing display illumination in the event of an alarm.
Two Potential-Free Change-Over Relays
One relay for the alarm, one relay for faults. 5 A switching current each, ideal for solenoid valves, gas boilers or building management systems.
Plain-Text Display
Shows system status, the mV-accurate sensor voltage and error codes.
48-Hour Relay Release
In the event of sensor failure the connected system continues to run while you replace the sensor. The remaining time is shown on the display.
Monitored Sensor Line
The integrated monitoring of the sensor line ensures operational safety. Cable break and sensor failure are reported.
Successor to the GX-A1
Identical connection positions, simple replacement in existing installations without rewiring.
Maintenance-Free µCtrl Technology
Microcontroller technology with built-in self-test of the internal systems.
What's in the Box
The device has no options and no additional variants. Sensors are ordered separately.
- Gas alarm control unit GX-A1+ (without sensor)
- Mounting material: 4 screws and 4 wall plugs for wall mounting
- Detailed operating instructions
The matching gas sensor is not included in the scope of delivery and must be selected separately depending on the gas type.
How the GX-A1+ Is Constructed
The device is housed in a light grey plastic enclosure with a removable front plate. At the front you see the display, indicators and buttons; inside are the connection terminals.
Housing with Front Plate
Four screws at the corners hold the cover shell. For wall mounting, loosen the screws, remove the cover shell and if necessary unplug the ribbon cable at the connector. The base shell with the screw terminals is then fixed to the wall.
Plain-Text Display
The backlit display with two lines of 16 characters each shows operating status, sensor voltage, alarm messages, error codes, temperature values, software version and alarm counter. The display texts are in English. In the event of an alarm the backlight flashes.
Three Status LEDs
The green LED “Operate” indicates operation, the yellow LED “Error” a fault and the red LED “Alarm” an alarm.
Piezo Signal Generator
The integrated signal generator behind the speaker grille emits the acoustic warnings, from a short tone for faults to the interrupted continuous alarm tone for the main alarm.
“Service” Button
In monitoring mode you browse through the 15 display pages with additional information and statistics. A longer press jumps back to the main display.
“Reset | Test” Button
With it you start the functional test of the internal systems. In the main alarm you mute the acoustic alarm with a press of two seconds.
Cable Entries at the Bottom
The cables are fed firmly as surface wiring from below. The threads are prepared for PG glands.
Connection Terminals in the Device
All connections are screw terminals: the mains terminals (L, N, PE), the terminals of the alarm relay Re1 and the fault relay Re2 (each G, Ö, S) as well as the sensor connection with +5 V, S, M and +24 V.
How the GX-A1+ Warns
The GX-A1+ evaluates the voltage supplied by the sensor. With passive sensors such as the GX-LNG the gas-sensitive tin oxide sits in a voltage divider whose partial voltage changes with the gas concentration. With active sensors such as the GX-CO2-30 a microcontroller generates this voltage.
Normal Operation
Display: “System: OK / Sensor: Ready”. The green LED lights, no tone is heard, both relays are energised.
Pre-Alarm (from 2.0 V)
Display: “PreAlarm !!!” with the sensor voltage in mV. Approx. every 10 seconds a double tone sounds, the relays remain energised.
Main Alarm (from 2.5 V)
Display: “Alarm !!!”, the red LED flashes, an interrupted continuous alarm tone sounds. The alarm relay Re1 drops out after about 10 seconds.
Fault
If the sensor voltage is too low the display shows “Sensor: Fault”. The yellow LED flashes, the fault relay Re2 drops out, approx. every 10 seconds a double tone sounds.
Sensor Failure
In the event of a cable break or total failure the display shows “System: Error / Sensor: Broken”. The yellow LED flashes, approx. every 30 seconds a short tone sounds.
Switching Delay
So that the relays do not chatter in the border range, they always switch with a delay of about 10 seconds.
Which Sensors Fit
For each gas type a suitable sensor must be used. Details on triggering and minimum concentration can be found in the operating instructions of the respective sensor. A current list of compatible sensors can be found on the manufacturer’s website, or you can obtain it from technical support.
GX-LNG (300897)
Town and natural gas, methane, butane, propane, LNG liquid gas and camping gas. Use with gas boiler and gas cooker.
GX-CFC (200901)
Refrigerants (chlorofluorocarbons). Use in air conditioning systems, cold stores and heat pumps.
GX-H2 (200616)
Hydrogen (H₂). Use in air conditioning systems and heat pumps.
GX-CO2-30 (300315)
Carbon dioxide in technical systems: dispensing systems, breweries, water carbonators, cold rooms and dry ice storage.
GX-CO2-25 (200989)
Carbon dioxide in room air: indoor spaces, workshop, open-plan office, waiting room, event rooms, classrooms and gymnasium.
This is a selection. For each sensor type a prescribed mounting height must be observed because gases have different properties. Take it from the operating instructions of the sensor used.
Mount Correctly, Connect, Commission
Installation must be carried out by a qualified specialist. Please observe the five safety rules.
Wall Mounting
- Loosen the four housing screws at the corners of the cover shell and remove the cover shell. If necessary unplug the ribbon cable at the connector.
- Fix the base shell to the wall with the enclosed mounting material. Choose the position so that the display is easy to read when standing.
- Feed the connection cables firmly as surface wiring from below.
- Insert the electronics and close the device.
Connections
- Sensor connection: +5 V (operating voltage), S (sensor input), M (ground), +24 V (operating voltage). A maximum of one sensor is possible
- Observe the colour coding of the sensor cable and the sensor specifications
- Relay connections per relay: G (common), Ö (normally closed), S (normally open)
- In monitoring mode the relay is energised: normally open contact closed, normally closed contact open
- In alarm or fault mode the relay drops out: normally open contact open, normally closed contact closed
- The maximum switching current of 5 A must not be exceeded
First Commissioning
- When mains voltage is applied an electrical functional test starts, then the warm-up phase of approx. 3 minutes. The display shows “System: OK / Sensor: Preheat”.
- As soon as the sensor has reached its operating temperature the display shows “Sensor: Ready”.
- After a power failure the test and warm-up phase are also restarted.
- If no sensor is connected or the sensor is defective the display shows “System Error / Sensor Broken”, the yellow LED flashes and approx. every 30 seconds a short alarm tone sounds.
Functional Test of the Internal Systems
- To protect your ears cover the sound opening of the piezo alarm generator with one hand and hold the “Reset | Test” button pressed.
- After a few seconds delay each time the following happens in succession: The alarm tone sounds continuously, the green and yellow LEDs light, the red LED and the display illumination flash. Then the fault relay Re2 drops out, then the alarm relay Re1.
- After releasing the button Re2 energises again immediately, LEDs, display and alarm generator return to the normal state, then Re1 also energises again.
This checks that all acoustic and optical alarms and the switching of the relays including delays work properly. If the test is started in the “Pre-Alarm” phase no alarm tone is heard. The connected sensor is not tested at the same time. How to test it is stated in the operating instructions of the sensor.
Mute Alarm, Service Pages, Sensor Failure
Mute Acoustic Alarm
During the main alarm a press of two seconds on “Reset | Test” only silences the acoustic alarm. The alarm relay remains dropped out and the optical warning remains. For the duration of the press the fault relay Re2 drops out briefly to inform the building management system and its recording of the acknowledgement.
The 15 Display Pages of the Service Button
- Main screen “System: OK / Sensor: Ready”
- Product Type: Series of the warning system
- Software Version
- On Time: total switch-on time
- Last Error Code: last error code
- Sensor Voltage: currently measured sensor voltage
- Voltage at Alarm: no function in this software version
- Error Counter: total counted errors
- Starts Counter: number of switch-on processes
- System Temp: operating temperature in the housing
- Chip Temp: temperature in the processor
- Last Error @: how long there has been no error
- Max Chip Temp: maximum processor temperature
- Max System Temp: maximum housing temperature
- Alarm Count ext: total counted alarms
For some counters a number is often already present because every device is tested before delivery. Keep the information from the service pages ready when you call technical support.
Sensor Failure: 48 Hours Time for Replacement
Sensors have a limited service life. So that for example a heating system can continue to run even without a sensor, press the “Service” and “Reset | Test” buttons simultaneously for at least 5 seconds until the display shows “Sensor Broken”. The fault relay Re2 remains dropped out and the alarm tone continues to sound every 30 seconds. The alarm relay Re1, however, energises again so that a device connected to it can continue to run for 48 hours. The lower display line shows the countdown, for example “Broken48”. During this time you replace the sensor.
Control External Devices
The two potential-free change-over relays switch on alarm or on fault. When connecting accessory devices, observe that the maximum switching current of 5 A must not be exceeded.
- Relay Re1 “Alarm”: switches on main alarm
- Relay Re2 “Fault”: switches on technical faults that the device itself detects
- Shut-off of a gas boiler
- Magnetic shut-off valve in the gas supply line
- Signal horn or warning light
- Ventilation system
- Building management system and home automation
- Telephone dialler and bus interface modules
Where the GX-A1+ May Be Used
- Only in dry indoor rooms of residential buildings and rooms with residential-like use
- Residential buildings and areas such as houses, apartments and rooms
- Sales areas such as shops and hypermarkets, rooms of the catering trade, small breweries and wine cellars
- Rooms of small businesses such as workshops, service centres and public authorities
- Technical rooms, areas with CO₂ cylinders, dispensing systems and dry ice storage
- Read the operating instructions thoroughly before installation and commissioning and keep them
- Packaging material is not a children’s toy and does not belong in children’s hands
- The manufacturer is not liable for damage or losses arising from the fact that no alarm signal is given despite an elevated gas concentration
What the GX-A1+ Does Not Do
- It only works with a connected sensor. Without a sensor it cannot detect any gas
- A maximum of one sensor can be connected
- It is not approved for potentially explosive atmospheres
- The protection class of the standard device is IP 20, for dry indoor rooms. A version in IP 65 is possible on request; please enquire with the manufacturer before ordering
- It does not switch systems off by itself. Solenoid valve or gas boiler must be connected via the relay
- The functional test only checks the internal systems, not the sensor
- The maintenance cycle depends on the connected sensor and the ambient conditions
- For carbon monoxide there are separate, specialised gas warning devices of the GX-C300 series
Detect and Classify Errors
In the event of a fault the fault relay Re2 drops out and the yellow LED “Error” flashes or lights. Press the Service button until the display shows “Last Error” with a number, and give this number to technical support.
External Causes
1 internal supply voltage too low. 2 mains supply too low. 3 sensor or sensor line defective. For these codes there is no special LED indication.
Ambient Temperature
23 ambient temperature too low. 24 ambient temperature too high. The yellow LED lights continuously.
Sensor Test
12 sensor test failed (no special LED indication). 25 sensor test failed, the yellow LED flashes rapidly.
LED Errors (4 to 9)
The yellow, red or green LED cannot be switched on or off. There is no special LED indication.
Internal Output Error
10 and 11: internal output error, no special LED indication.
Memory and Software
21 memory initialisation failed. 22 internal software error. 26 temperature sensor error. 27 memory error detected. The yellow LED flashes slowly.
Clean and Find Faults
Clean and Maintain
- Keep moisture (splash or rain water), dust and direct sunlight away from the device
- Clean the device only with a dry linen cloth; in case of heavy soiling it may be slightly dampened
- Do not use solvent-containing cleaning agents
- Check the sensor regularly in accordance with its operating instructions
Troubleshooting
“Sensor: Broken” on the Display?
No sensor is connected, the sensor is defective or the sensor line is interrupted. Check the connection and cable. If necessary use the 48-hour relay release.
Yellow LED Flashes?
The device has detected a fault or a sensor error. Call up “Last Error” via the Service button and give the number to support.
“Sensor: Preheat”?
The sensor is warming up. The warm-up phase lasts approx. 3 minutes and also restarts after a power failure.
Alarm Is Mute but Relay Dropped Out?
The acoustic alarm was muted with the Reset function. The alarm relay remains dropped out and the optical warning remains.
If the fault persists, contact the manufacturer and keep the information from the service pages ready.
In Case of Service and Return
- Get in touch if the device is defective and state your complete address as well as the reason for return.
- Within Germany the manufacturer will send you a free return label by e-mail.
- Pack the device adequately. Enclose a fault description, proof of purchase as well as your address and delivery address (name, telephone number, street, house number, postcode, city, country).
The manufacturer cannot accept unfree parcels. Unauthorised returns that do not constitute a complaint will be charged subsequently. The manufacturer accepts no liability for damage or loss during shipping.
Warranty, Guarantee and Disposal
The GX-A1+ is covered by the statutory warranty of at least 2 years in the EU. In the event of material defects and quality deficiencies the manufacturer repairs or replaces the device free of charge provided it has been used in accordance with the operating instructions. The manufacturer is not liable for damage due to accident, misuse, alteration or negligence. In addition, Elektrotechnik Schabus offers a 5-year guarantee that can be registered online. Repair and spare parts are available directly from the manufacturer, even beyond the statutory warranty.
The device bears the CE marking. The CE declaration, the operating instructions and the mounting drawing can be found on the manufacturer’s website.
The GX-A1+ does not belong in household waste. The crossed-out waste bin symbol on the product reminds you to use the take-back systems so that the materials can be reused in an environmentally friendly manner at the end of the service life (WEEE Reg. No. DE91394868). Further information is available from the waste advice centre of your city or from the manufacturer.
Why the GX-A1+ Is Suitable
One Control Unit, Many Gases
Usable with the matching sensor for natural gas, liquid gas, CO₂, hydrogen or refrigerants.
Sensor Freely Placeable
The sensor is located where the gas collects, independently of the control unit.
Plain Text Instead of Guesswork
Display with system status, sensor voltage and error codes.
Automatic Shut-Off
Two potential-free change-over relays for valves, boilers and building management systems.
48 Hours Breathing Space for Sensor Replacement
Connected systems continue to run in the event of sensor failure; the remaining time is shown on the display.
From the Manufacturer
Personal expert advice, 5-year guarantee registrable, repair and spare parts directly from the manufacturer.
Application Areas
- Gas boilers and gas cookers in apartments and houses
- Technical rooms with gas connection
- Catering, dispensing systems and breweries
- Monitoring of CO₂ cylinders and water carbonators
- Cold rooms and rooms with dry ice storage
- Air conditioning systems, cold stores and heat pumps with refrigerant
- Workshops, service centres and public authorities
- Room air monitoring in offices, classrooms and event rooms
The Schabus GAS ALARM GX-A1+: Invisible gas, visible safety.
Frequently Asked Questions
How does the GX-A1+ work?
The GX-A1+ supplies an external gas sensor with operating voltage and continuously evaluates its voltage. From 2.0 V it triggers a pre-alarm, from 2.5 V the main alarm. It warns acoustically and optically and switches the potential-free alarm relay. A second relay reports faults.
Which gases can the GX-A1+ detect?
This depends on the connected sensor: natural and town gas (methane, propane, butane, LNG), carbon dioxide, hydrogen and refrigerants such as R32, R404a or R410a. For each gas type a suitable sensor must be used.
What is included in the scope of delivery?
The gas alarm control unit GX-A1+ without sensor, mounting material (4 screws and 4 wall plugs for wall mounting) and the detailed operating instructions. Please order the sensor separately.
Which sensors are compatible?
For example GX-LNG (300897) for town and natural gas, GX-CFC (200901) for refrigerants, GX-H2 (200616) for hydrogen, GX-CO2-30 (300315) for CO₂ in technical systems and GX-CO2-25 (200989) for CO₂ in room air. A current list can be found on the manufacturer’s website.
How many sensors can I connect?
A maximum of one sensor is possible.
Where must the sensor be mounted?
The sensor can be positioned independently of the control unit. For each sensor type a prescribed mounting height must be observed because gases have different properties. Take it from the operating instructions of the sensor used.
What does the display show?
The illuminated display with two lines shows operating status, sensor voltage in mV, alarm messages, error codes, temperature values, software version and alarm counter. The display texts are in English. With the Service button you browse through 15 display pages.
What do the three LEDs mean?
Green “Operate” indicates operation, yellow “Error” a fault and red “Alarm” an alarm. In the main alarm the red LED flashes, in the event of a sensor failure or a fault the yellow LED flashes.
What happens if the sensor fails?
The display shows “Sensor: Broken”, the yellow LED flashes and every 30 seconds a short tone sounds. With the 48-hour relay release (press “Service” and “Reset | Test” buttons simultaneously for at least 5 seconds) a connected system remains in operation for 48 hours. The remaining time is shown on the display.
How do I test the device?
Hold the “Reset | Test” button pressed and cover the sound opening with one hand. Alarm tone, LEDs, display illumination and both relays are checked in succession. The sensor is not tested at the same time; for that observe the instructions of the sensor.
How do I switch off the alarm tone?
During the main alarm press the “Reset | Test” button for two seconds. Only the acoustic alarm is muted. The alarm relay remains dropped out and the optical warning remains.
Which external devices can I connect?
Via the potential-free change-over relays you control for example magnetic shut-off valves, gas boilers, ventilation systems, signal horn or warning light, telephone diallers, bus interface modules and building management systems. The maximum switching current of 5 A must not be exceeded.
Why does it take time after switch-on until the device is ready?
After applying mains voltage a functional test runs, then a warm-up phase of approx. 3 minutes. The display shows “Sensor: Preheat” until the sensor has reached its operating temperature, then “Sensor: Ready”. The same happens after a power failure.
Can I use the GX-A1+ in place of the GX-A1?
Yes. The GX-A1+ is the 100 % compatible successor to the GX-A1 with identical connection positions. Replacement in existing installations is possible without rewiring.
Where may the device be used?
In dry indoor rooms of residential buildings and rooms with residential-like use, in sales areas, catering, small breweries, wine cellars, workshops, service centres and public authorities. Not in potentially explosive atmospheres. By default the housing has protection class IP 20; a version in IP 65 is possible on request.
Can I monitor carbon monoxide with it?
For carbon monoxide there are according to the manufacturer separate, specialised gas warning devices of the GX-C300 series.
Are there options or additional variants?
No. The GX-A1+ has no options. The gas sensor is separate accessories.
How long is the guarantee valid?
The statutory warranty of at least 2 years in the EU applies. In addition, the manufacturer Schabus offers a 5-year guarantee that can be registered online.
Questions about the gas alarm GX-A1+?
Our support team in Germany advises you free of charge on selection, installation and configuration.
Gas Alarm Control Panel GX Series
The gas alarm control panel of the GX series is designed for the reliable detection of gases and gas mixtures in industrial, laboratory, and technical areas. It enables the triggering of alarm and fault signals via potential-free relay contacts and can be operated with one sensor. The illuminated display clearly shows status and warning messages.
Technical Data
- Operating voltage: 110 ... 240 V~ / 50–60 Hz
- Power consumption: 2 ... 10 VA (depending on operating condition)
- Relay contacts: 2x potential-free changeover contacts (n.o. / n.c.)
- Relay Re1 “Alarm”: 250 V~ / 5 A / fused
- Relay Re2 “Fault”: 60 V= / 5 A / fused
- Sensor connections: max. 1 sensor
- Sensor operating voltage: 5 V= / max. 300 mA
- Evaluation: voltage / ADC
- Sound pressure piezo alarm: 85 dB(A) @ 1 m
- Display: 2x16 characters, white on blue, backlit, flashes during alarm, text in English
- LED indicators: green (operation), yellow (fault), red (alarm)
- Temperature range: -10 °C ... +50 °C
- Humidity: 10%rH ... 90%rH (non-condensing)
- Protection class: IP20 (optional IP65 with surcharge)
- Connection type: screw terminals (all connections)
- Installation: fixed wiring conduit (surface-mounted, feed from below)
- Housing: thread prepared for PG fittings
- Dimensions (H x W x D): 80 x 160 x 55 mm
Available Sensor Types
- GX-LNG 300897: detection of town gas and natural gas (methane, butane, propane, ethanol ...)
- GX-CFC 200901: detection of refrigerants (R22, R32, R404a, R410a, R1234yf ...)
- GX-CO2-25 200989: detection of CO₂ from exhaled air (alarm threshold: 2500 ppm)
- GX-CO2-30 300315: detection of CO₂ from technical systems under pressure (alarm threshold: 3% vol.)
Manufacturer information:
Electrical engineering Schabus GmbH & Co. KG
Baierbacher Straße 150
83071 Stephanskirchen
Germany
Telephone: +49 80 36 / 674 979 – 0
Email: info@elektrotechnik-schabus.de
Responsible person:
Didactum® Security GmbH
Im Mühlenfeld 4
48163 Münster
Deutschland
Fon:
(+49) 250 19 71 63 54 / (+49) 171 33 11 577
Email: info@didactum-security.de