€184.00
AKCP In-Line Power Meter – Professional Power Monitoring and Switching Control
The AKCP In-Line Power Meter Sensor revolutionizes the way companies perform their power consumption measurement and energy monitoring. These highly accurate power meters provide a comprehensive solution for energy efficiency in data centers, server rooms, and industrial applications.
Precise Energy Monitoring for Maximum Efficiency
The AKCP In-Line Power Meter Sensor is installed directly between the power source and the PDU or individual device, continuously monitoring critical parameters such as voltage (V), current (A), and kilowatt-hours (kWh). With its billing-grade precision, the system enables accurate identification of power-hungry devices and offers the possibility for remote switching of devices.
The available models with 16A and 32A current load capacity cover a wide range of industrial requirements. The input voltage rating of 100V to 250V AC makes the devices universally suitable for various international power standards.
Versatile Connection Options for Every Need
A standout feature of the ILPM series is the wide variety of available plug connections. The system supports various plug types, including:
- NEMA L5-20, L6-30, and 5-20 for North American standards
- IEC P+N+E, C13/C14, and C19/C20 for international compatibility
- UK BS1363, Schuko CEE 7/7 for European requirements
- Australian plugs for the Asia-Pacific market
This comprehensive compatibility makes the In-Line Power Meter the ideal solution for globally operating companies with heterogeneous infrastructures.
Please note:
The options listed above are special features. There are many more options available to personalize the In-Line Power Meter Sensor. To obtain further options, please contact us.
Intelligent Switching Functions and Relay Technology
With a contact load of 40 amperes, a mechanical service life of 10⁷ switching cycles, and an electrical service life of 3×10⁴ cycles, these relays offer the highest reliability for critical applications.
Advanced Environmental Monitoring
In addition to pure power monitoring, the system offers optional Cabinet Thermal Maps (-CTM or -CTHM) with integrated temperature and humidity sensors. The temperature range from -40°C to +75°C and humidity measurement from 0 to 100% relative humidity enable comprehensive environmental monitoring for optimal operating conditions.
Practical Application Areas
The In-Line Power Meters are essential for various application scenarios:
Circuit Breaker Monitoring: Continuous control of how close the current consumption is to tripping the fuse prevents unplanned outages.
Capacity Planning: Ensuring sufficient power reserves when adding new devices to existing circuits.
Cost Transparency: Precise billing of individual customers in co-location services through accurate consumption measurement.
Centralized Monitoring: Monitoring up to 16 devices via a single IP address reduces complexity and administrative effort.
Technical Specifications and Reliability
The compact design with dimensions of 170 x 85 x 52 mm allows flexible installation even in tight spaces. With a typical power consumption of only 800 mW (160 mA) and a peak consumption of 1.75 watts (350 mA), the system operates extremely energy-efficiently.
Communication is via RJ-45 connector with UTP CAT5e/6 cables at a maximum cable length of 32 feet (10 meters). Power is supplied directly via the sensorProbe+ family, so no additional power supply is required.
Long-Term Operational Safety
The use of highly integrated, energy-saving surface-mount technology ensures long-term reliability. With an MTBF of 1,400,000 hours, based on field experience with sensorProbe units, the system offers exceptional operational safety.
The operating temperature range of -35°C to 80°C and humidity tolerance of 20% to 80% (non-condensing) make the system suitable for a wide range of environmental conditions.
The AKCP In-Line Power Meters represent a future-proof investment in professional energy management systems and provide the necessary transparency and control for modern infrastructures.
- Measurements
- Input voltage rating: 100V~250V AC
- Current rating: 1 Phase - 16A or 32A
- Voltage measurements (V): Voltage (V), Current (A), Active power (kW), Total active energy (kWh), Leakage current (A), Power factor
- Power rating
- 1 Phase - 16A or 32A
- 100V~250V AC
- Environmental monitoring
- Optional cabinet thermal card (-CTM or -CTHM): Temperature sensor, humidity sensor
- Range: -40°C to +75°C, 0 to 100% relative humidity
- Control
- Interlocked relay
- Switching relay
- Contact rating: 40 Ampere
- Mechanical life: 1×10^7 times
- Electrical life: 3×10^4 times
- Class: B
- Status indication
- LED display for power supply
- LED relay status (with optional relay)
- Inputs
- 1x sensor RJ45 port
- Outputs
- Hardwired with the following plugs: IEC 60320 C20, IEC 60320 C14, Nema 5-15P, Nema 5-20P, Nema 5-30P, Nema L5-15P, Nema L5-20P, Nema L5-30P, UK BS, Shuko CEE 7/7 plug, IEC60309 2P+E blue
- Socket types: IEC 60320 C13, IEC 60320 C19, Nema 5-15R, Nema 5-20R, Nema 5-30R, Nema L5-20R, Nema L5-30R, UK BS1363, Shuko CEE 7/3 socket, IEC 60309 2P+E Blue
- Interface
- Communication cable: RJ-45 socket to sensor via UTP CAT5e/6 cable
- Power supply
- Power source: Power supply via the sensorProbe+ family. No additional power supply required
- Power consumption: Typically 800 mWatt, 160 mA
- Peak: 1.75 watt, 350 mA
- Maximum cable length
- Run length is 32 feet (10 meters) with approved low-capacity shielded cable or UTP
- Dimensions
- Size: 170 x 85 x 52 mm
- Mounting
- Keyhole mounting
- Components
- Manufactured with highly integrated, power-saving surface-mounted components for long-term reliability
- Operating environment
- Temperature: Min. -35° C – Max. 80° C
- Humidity: Min. 20% – Max. 80% (non-condensing)
- MTBF
- 1,400,000 hours based on field experience with sensorProbe units
- Important note
- sensorProbe+ units automatically detect the presence of the ILPM sensor
- The ILPM sensor is only compatible with sensorProbe+ platform units
- Upon first connection or after upgrading a sensorProbe+ unit, the sensor firmware may be updated by the unit and may not be immediately available
- With sensorProbeX+, the sensor can only be used on the main module sensor ports
- Number of sensors
- ILPM: 5, ILPM-LR: 6, -CTM: +9, -CTHM: +11
Manufacturer information:
AKCess Pro Ltd.
267/4 Soi Sichon, Sutthisan Rd., Samsen Nok
Huai Khwang Bangkok, 10310
Thailand
Email: sales@akcp.com
Responsible person:
Didactum® Security GmbH
Marsweg 17
48163 Münster
Deutschland
Fon: +49 - 2501 - 9 78 58 80
Email: info@didactum-security.de