€450.80
AKCP Fuel and Oil Sensor (ropeFuel Sensor FLKS)
Innovative Leak Detection Technology for Critical Infrastructures
The AKCP ropeFuel Sensor (FLKS) from the renowned manufacturer AKCP is a state-of-the-art rope-style fuel sensor and leak detector, specifically developed for the professional monitoring of fuel and oil leaks. This intelligent sensor system can be seamlessly connected to any RJ-45 intelligent sensor port of the proven AKCess Pro sensorProbe or securityProbe alarm servers and enables reliable detection of fuel, oil, and other liquid hydrocarbons.
Please note:
Longer cable versions are available for this sensor. Please inquire about these by email or telephone.
Precise Leakage Detection Along the Entire Sensor Length
The fuel and oil sensor is characterized by its exceptional ability to detect the presence of liquid hydrocarbon fuels at any point along its entire length. In combination with the AKCP sensor module, the system not only detects the presence of leaks but also automatically triggers an alarm and determines the exact location of a leak with an impressive accuracy of one meter or one foot.
Versatile Fuel Detection for Various Applications
The leak detector has been developed to detect a wide range of fuels and oils. Typically, this highly sensitive sensor can reliably detect the following substances:
- Gasoline (response time: 2–12 minutes depending on grade and type)
- Diesel #1 (response time: 60 minutes)
- Jet A/B/5/8 (response time: 50–70 minutes)
- JP-4/5/7 (response time: 15–70 minutes)
- Kerosene (response time: 47 minutes)
Ideal Application Areas for Maximum Safety
As this oil leak sensor is designed as a flexible rope system, it is ideally suited for installation beneath tanks and is preferred for diesel generators at remote locations. In such critical environments, early alarm notification in the event of fuel spillage or fuel theft is crucial for maintaining continuous power supply. The sensor provides distributed leak detection for various applications such as:
- Monitoring fuel leaks under or around emergency generator tanks
- Fuel storage areas and fueling station monitoring
- Fuel transfer stations and distribution facilities
- Industrial plants with critical fuel systems
Technical Specifications of the AKCP ropeFuel Sensor
Basic Properties
- Sensor type: Wet/Dry Open/Closed contact input switch
- Measurement rate: Multiple measurements per second
- Operating temperature range: -20°C to 60°C (4°F to 140°F)
- Tensile strength limit: Maximum 50 lb
- Minimum bending radius: 2 inches (50 mm)
- Pressure load: Loads over 20 lb (9 kg) per linear inch at 20°C can trigger an alarm immediately
Technical Data and Compatibility
- Power supply: Provided by sensorProbe or securityProbe (typically 125 mWatt, 25 mA)
- Interface: RJ-45 socket with UTP Cat 5 cable
- Maximum cable length: Up to 100 feet (30 meters) expandable with standard CAT5/6 LAN cable
- Available lengths: 1 to 5 meters available to order
- Standard connection cable: 20-foot (6.1 meter) non-sensing lead-in cable
- Dimensions: 56 x 55 x 33.3 mm
- Cable diameter: 0.28 inch (7 mm) nominal
Intelligent Functions and Monitoring
- Auto Sense function: Automatic identification of the fuel and oil sensor
- Web interface integration: Full status message in case of tampering or cable break
- SNMP support: OID (.1.3.6.1.4.1.3854.1.2.2.1.18.1.3.0) for seamless integration into network management systems
- LED status display: Visual indication of sensor status
- Disconnect alarm: Automatic detection of connection interruptions
Mounting and Installation
The AKCP fuel sensor can be installed using both DIN rail mounting and screw mounting. The system is delivered fully assembled and includes the rope sensor part (the liquid detection line), the non-sensing lead-in cable from the rope to the sensor module, and the main sensor module. Additionally, a 5-foot CAT5 extension cable is included in the scope of delivery.
Important Safety Instructions and Operating Guidelines
- Single use: The AKCP ropeFuel Sensor is designed for single use only and must be completely replaced after contact with hydrocarbon liquids. Cleaning or reuse is not possible and not recommended.
- Installation instructions: AKCP expressly recommends not placing the ropeFuel Sensor on conductive surfaces to avoid false alarms and malfunctions.
- Ordering instructions: When ordering, please specify the specific fuel type or oil type as well as the corresponding oil grade to ensure optimal detection performance. It is important to note that water is not detected by the fuel and oil sensor.
Compliance and Standards
The AKCP ropeFuel Sensor complies with the ASTM D 543 standard and is fully compatible with all current AKCP sensorProbe2/8 and securityProbe alarm server systems. This certification ensures the highest quality and safety standards for critical monitoring applications.
Reliable Fuel Monitoring for Critical Applications
The AKCP ropeFuel Sensor is an indispensable solution for companies and facilities that rely on continuous fuel supply. With its precise leak detection, flexible installation, and seamless integration into existing monitoring systems, it provides maximum security and reliability for critical infrastructures.
- Measurement Range
- Wet or Dry
- Sensor Type
- Normally Open/Closed contact input switch
- Measurement Rate
- Multiple measurements per second
- Response Time
- Can detect the presence of fuel and oil at a specific location within 1 meter or 1 foot along the length of the sensor cable
- Typical response time at 20°C (68°F):
- Gasoline: 2-12 minutes (depending on grade and type)
- Diesel #1: 60 minutes
- Jet A\B\5\8: 50-70 minutes
- JP-4\5\7: 15-70 minutes
- Kerosene: 47 minutes
- Non-resettable
- Must be replaced after contact with hydrocarbon liquids
- Display
- LED for status
- Operating Temperature
- -20°C to 60°C
- 4°F to 140°F
- Tensile Strength Limit
- Do not exceed 50 lb
- Bend Radius
- 2 inches (50 mm) minimum
- Pressure
- Loads greater than 20 lb (9 kg) per linear inch at 20°C (68°F) may immediately trigger an alarm
- Interface
- RJ-45 socket to sensor via UTP Cat 5 cable
- Communication Cable
- Max. cable length: The FuelRope sensor can be extended from the RJ-45 Intelligent Sensor Ports on the base units up to 100 feet or 30 meters with standard CAT5/6 LAN cable
- Delivered fully assembled and includes the rope section (liquid-detecting cable), the non-detecting lead cable (from the rope to the sensor module), and the main sensor module
- Includes a 5-foot CAT5 extension cable
- Detecting rope cable can be pre-ordered from a minimum of 1 meter up to any individual length up to 5 meters
- Non-detecting cable comes in a standard length of 20 feet
- Power Supply
- Powered by the control unit. No additional power supply required
- Full auto-detection including separation alarm
- Power consumption: Typically 125 mWatt, 25 mA
- Dimensions
- 56 x 55 x 33.3 mm
- Mounting
- DIN rail mounting
- Screw mounting
- Cable Diameter
- 0.28 inches (7 mm) nominal
- Important Notes
- The AKCP ropeFuel sensor is in most cases intended for single use only and must be replaced after contact with hydrocarbon liquids
- AKCP does not recommend placing the ropeFuel sensor on a conductive surface
- Number of Sensors
- 1
Manufacturer information:
AKCess Pro Ltd.
267/4 Soi Sichon, Sutthisan Rd., Samsen Nok
Huai Khwang Bangkok, 10310
Thailand
Email: sales@akcp.com
Responsible person:
Didactum® Security GmbH
Marsweg 17
48163 Münster
Deutschland
Fon: +49 - 2501 - 9 78 58 80
Email: info@didactum-security.de