Sensor 60V: Precise Voltage Monitoring for Industrial Applications
The Sensor 60V is a galvanically isolated voltage sensor designed for measuring DC voltages in the range of 0 to 60 V DC (including negative voltages from 0 to -60 V DC). This sensor is ideal for voltage monitoring in server rooms, data centers, telecommunication facilities, and other technical environments. Via the 1-Wire UNI bus (RJ11), the sensor can be connected to devices such as Poseidon2 or Ares, making the data accessible via LAN or GSM. Typical applications include measuring battery voltages or industrial sensors with a 0-10V output, especially in telecommunications with the -48V standard.
Main Features of the Sensor 60V 1W-UNI v2
The Sensor 60V 1W-UNI v2 converts DC voltage signals into the 1-Wire UNI format (RJ11) and offers precise mains voltage measurement. The galvanic isolation ensures maximum safety and reliability. Here is an overview of the key features:
- Precise Voltage Measurement: The 60V DC sensor measures voltages from 0 to 60 V DC (also negative voltages from 0 to -60 V DC) with an accuracy of 2% and a resolution of 0.1 V, ideal for industrial applications such as battery voltage or 0-10V sensors.
- Galvanic Isolation: The 0-60V input is electrically isolated from the 1-Wire UNI bus (RJ11), preventing interference and increasing safety.
- Compatibility: Compatible with HW group devices such as Poseidon2, Ares, STE2, SiteMon5, and other 1-Wire UNI systems, for seamless Poseidon2 integration via LAN or GSM.
- Power Supply: Bus-powered via the 1-Wire UNI bus (max. 2 sensors per active port) or via an external 5V DC power adapter for increased performance.
- Calibration: Equipped with an 8-point calibration table that can be adjusted with the 1W-UNI USB calibrator to optimize readings for specific industrial sensors.
- Compact Design: With two RJ11 connectors for daisy-chaining and compact dimensions, the sensor is space-saving and flexible (max. cable length 60 m).
Application Areas of the Sensor 60V 1W-UNI v2
The Sensor 60V 1W-UNI v2 is versatile and suitable for scenarios where precise voltage monitoring is required. Typical application areas include:
- Telecommunications: Monitoring of -48V DC power supplies in telco applications (e.g. battery voltage in UPS systems).
- Server Rooms and Data Centers: Measuring the voltage of 12V or 48V batteries to ensure operational reliability.
- Industrial Applications: Connecting 0-10V sensors (e.g. pressure, level, or temperature sensors) for process control.
- Remote Monitoring: Email or SMS notifications when values are outside the “SafeRange” to protect critical systems.
- Energy Monitoring: Integration into systems for monitoring energy flow in buildings or facilities.
Why is the Sensor 60V 1W-UNI v2 the Right Choice?
The Sensor 60V 1W-UNI v2 stands out for its high precision and easy integration. Compared to other signal converters, it offers galvanic isolation, high accuracy (also for 0-10V sensors), and compatibility with a wide range of HW group devices. The possibility of daisy-chaining and flexible power supply (bus-powered or external) make it ideal for industrial environments. The 1-Wire UNI interface allows easy connection to monitoring systems such as Poseidon2 or Ares, while the calibration option enables adaptation to specific sensors.
Technical Details
- Input: 0-60 V DC (also negative voltages 0 to -60 V DC)
- Interface: 1-Wire UNI (2x RJ11 for daisy-chaining)
- Power Supply: Bus-powered via 1-Wire UNI (max. 2 sensors per port) or external 5V DC power adapter
- Measurement Accuracy: 2% of the full range
- Resolution: 0.1 V
- Connection: 2-pin terminal block (V+, V-)
- Operating Environment: -30 °C to +85 °C, 0% to 100% relative humidity
- Protection Class: IP20
- Dimensions: 65 x 80 x 30 mm
- Weight: 200 g
- Max. Cable Length: 60 m (total cable length from the active port)
Integration with HW group Products
The Sensor 60V 1W-UNI v2 is optimally matched to HW group devices such as Poseidon2, Ares, STE2, or SiteMon5. In combination with these devices, you can build a comprehensive energy monitoring system that provides measurement data in real time via LAN, GSM, SNMP, or Modbus/TCP. The free HWg-PDMS software enables analysis and export of data to Excel for detailed reports. Connection to the SensDesk portal (paid) offers additional visualization options via Android or iOS apps.
Installation and Setup
Installation of the sensor is straightforward. Connect the voltage source to the 2-pin terminal block (V+, V-), connect the RJ11 output to the monitoring system, and the sensor will be powered via the 1-Wire UNI bus or an external 5V DC adapter. Thanks to the compact design and the possibility of daisy-chaining (max. 2 sensors per active port), the sensor can also be used in confined spaces. For higher power requirements, the “1-Wire Hub Power” is recommended. Calibration can be adjusted with the 1W-UNI USB calibrator to ensure precise measurements.
The HW group Sensor 60V 1W-UNI v2 is the ideal solution for precise voltage monitoring and remote monitoring in industrial applications, especially in telecommunications -48V.
With its galvanic isolation, high accuracy, and flexible interfaces, it is perfect for server rooms, industrial facilities, and battery voltage monitoring. Optimize your monitoring systems with the Sensor 60V 1W-UNI v2.
Datasheet 1
Bus System:
- Type: 1Wire-UNI (RJ11)
- Connection: 2x RJ11 (Sensors can be connected in series)
- Maximum distance: 60m (total cable length from the active port)
- Compatible with: Poseidon2 xxxx, Ares xx, Poseidon 2250, Poseidon 4002, SiteMon5
Power Supply:
- Primary: 1Wire-UNI Bus
- External: 5VDC external power supply possible
- Power limit: One active RJ11 port can supply a maximum of two sensors
- Power boost: "1-Wire hub Power" or external power supply required for more sensors
Sensor Input:
- Connection: 2-pin terminal block (V+, V-)
- Measuring range: 0 to 60VDC (max. 70V)
- Applications: 0-1V, 0-10V, -48V DC, 0-60V
- Accuracy: 2% of the full 60V range at 25°C
Sensor Output:
- Resolution: 1 decimal place
- Units: Standard [V], conversion possible (e.g. [m], [mm], [hPa], [ppm])
- Measurement period: Once per second
Electrical Isolation:
- 1Wire-UNI bus is electrically isolated from the 0-60V input
- 0-60V input electrically isolated from 1Wire-UNI (RJ11)
Environmental Conditions:
- Operating temperature: -40°C to +85°C (-40°F to +185°F)
- Relative humidity: 5% to 70% RH
Mechanical Data:
- Dimensions: 65 x 80 x 30 mm
- Weight: 200 g
- Connection for external 5V power supply available
Calibration and Conversion:
- Calibration tool for MS Windows
- Calibration to curve with 8 different points possible
- Conversion from input voltage [V] to output unit (e.g. [mm], [hPa], [m], [ppm])
- Conversion directly in the sensor for correct display in emails, SMS, or web interface
Applications:
- Signal converter for 0-10V industrial probes
- Battery monitoring in telecommunication systems (-48V standard)
- Independent measurement of individual battery cells
- Voltage measurement of 12V or 24V car batteries
- Connection of industrial sensors to Poseidon2 or Ares units
Related Products:
- Sensor 4-20mA 1W-UNI: 4-20mA current loop sensor
- Sensor 0-20mA 1W-UNI: 0-20mA sensor for 1Wire UNI bus
- Converter 2xPt100 1W-UNI: Converter for Pt-100/1000 probes
- 30A Current probe 1W-UNI: 0-30AAC sensor with current clamp
- 1W-UNI USB calibrator: USB-RJ11 cable + software for calibration
- 1-Wire hub Power: Hub for 1 to 8 sensors with external power supply
Monitoring devices
Other available sensors
Extension units
Accessories
Mounting Plate D Bracket for Ares and Poseidon2 Operating environment: -3°C - 85°C / 0%RH - 100%RH Storage environment: -30°C - 60°C / 5%RH - 95%RH Dimensions: 74 x 6 x 120 (W x H x D) / 58g Warranty: 24 months Wall mounting plate for Ares, Poseidon2 3266/68 and other products.
DB9 LapLink Cable 2m A LapLink cable (also known as Lablink or null-printer cable) is a cable used to connect two computers directly via a cable connection. Housing: Plastic Type: Cable
DIN-Rail Box Set A mounting kit for installing HW-group devices on a DIN rail. Applications and Use: Mounting kit for installing HW-group devices with metal housing on a DIN rail. Operating environment: -30°C - 85°C / 0%RH - 100%RH Storage environment: -30°C - 60°C / 5%RH - 95%RH Dimensions: 45 x 11 x 105 (W x H x D) / 22g
Mounting Kit Screw set for mechanical mounting Applications and Use: Screw set for mechanical fastening
Mounting Plate E- 1U Rack (cabinet) mounting plate, 1U mounting for HW-group Ares and Poseidon2 devices Operating environment: -30°C - 85°C / 0%RH - 100%RH Storage environment: -30°C - 60°C / 5%RH - 95%RH Dimensions: 127 x 45 x 94 (W x H x D) / 137g Warranty: 24 months Rack (cabinet) mounting plate, 1U mounting for HW-group Ares, Poseidon2 3266/3268 and other products.
Mounting Plate L DIN Rail DIN rail mounting plate for Ares, Poseidon2 3268, and other products. Features: Metal housing Wall mounting Applications and Use: Profiles for metal-encapsulated HWg devices for wall mounting. Dimensions: 150 x 120 x 45 (W x H x D) / 65g Warranty: 24 months
Mounting Kit for Poseidon2 4002 and HWg-SMS-GW3 Applications and Use: Mounting kit for Poseidon2 4002 and HWg-SMS-GW3 Operating environment: -30°C - 85°C / 0%RH - 100%RH Storage environment: -30°C - 60°C / 5%RH - 95%RH Dimensions: 136 x 45 x 16 (W x H x D) / 165g Warranty: 24 months
Rack Shelf 1U A versatile solution for easy mounting of HW-group devices in 1U racks. Operating environment: -30°C - 85°C / 0%RH - 100%RH Storage environment: -30°C - 60°C / 5%RH - 95%RH Dimensions: 485 x 44 x 104 (W x H x D) / 597g Warranty: 24 months Housing: Metal Type: Wall mounting This shelf makes it easy to use devices in racks. You can even combine different 1U products and sensors.
Software
Manufacturer information:
HW group s. r. o.
Rumunská 26
Prague, 120 00
Czech Republic
Phone: +420 222 511 918
Email: sales@hwg.cz
Responsible person:
Didactum® Security GmbH
Marsweg 17
48163 Münster
Deutschland
Fon: +49 - 2501 - 9 78 58 80
Email: info@didactum-security.de